Manual de Usuario NoBreak Tripp Lite 2,200VA SU2200XLA click aquí
Especificaciones NoBreak Tripp Lite 2,200VA SU2200XLA click aquí
Tabla tiempo de Respaldo Tripp Lite 2,200VA SU2200XLA click aquí
Link a la pagina del Fabricante click aquí
 |
 |
Tripp Lite's Smart Online SU2200XLa on-line, double
conversion UPS protects critical server, networking or telecommunications
equipment from blackouts, brownouts, voltage fluctuations and surges in an
attractive all-black upright tower form factor. Large capacity 2200VA/1600W
UPS continuously converts incoming AC to DC, then back to perfect sine wave
AC output at 120V AC (+/-2%). Removes harmonic distortion, fast electrical
impulses, frequency fluctuations and other hard-to-solve power problems not
addressed by other UPS systems. True sine wave output and zero transfer time
offers guaranteed compatibility with all equipment types. Includes 7 UPS
supported outlets. 2 three-outlet load banks can be independently controlled
via software interface to selectively reboot remote equipment or
automatically shed less critical loads to extend battery runtime for the
most critical equipment. Battery support can be extended with the addition
of external battery packs. Includes slot for internal SNMP/web card, plus
DB9 enhanced serial monitoring port for unattended shutdown, remote control
and monitoring of UPS system and power data. Network management interfaces
support simultaneous communications via USB port, DB9 serial port and
SNMPWEBCARD slot. HID-compliant USB interface enables integration with built-in
power management and auto shutdown features of Windows and Mac OS X.
Includes Tripp Lite's PowerAlert UPS Power Management Software. Compatible
with Tripp Lite's Watchdog Service Monitoring and Control Software.
Key Features
* True on-line, double conversion UPS provides a constant, pure sine
wave AC output
* Maintains continuous operation through blackouts, brownouts, voltage
fluctuations and surges with zero transfer time
* Zero transfer time, on-line, double-conversion and economy-mode operation
supported
* Removes harmonic distortion, electrical impulses, frequency variations and
other hard-to-solve power problems
* Accepts input voltages between 80V and 138V (65V to 138V at loads under
70%), regulating output to 120V AC +/-2%
* 2200VA/1600W output capacity with 7 total outlets (6 NEMA5-15/20R and 1
L5-20R)
* Two built-in individually switchable load banks, each with three outets,
can be controlled via software interface to selectively reboot remote
equipment or automatically shed less critical loads to extend battery
runtime for the most critical equipment
* Standard internal battery set provides 14 min. runtime at half load and
4.5 min. at full load
* Runtime is expandable with BP48V24-2U (limit 1) or BP48V60RT3U (multi-pack
compatible) external battery packs
* Attractive all-black upright tower format
* Simultaneous communications via HID-compliant USB port, serial port, and
SNMP/web card slot
* HID-compliant USB interface enables integration with built-in power
management and auto shutdown features of Windows and Mac OS X
* DB9 serial network interface supports RS-232 and contact closure messaging
* Slot for optional SNMP/web card (part #: SNMPWEBCARD)
* Included PowerAlert UPS Power Management Software and cabling provides
monitoring of in-depth site power conditions, full UPS status and fault
warnings, output load level and load bank power control
* Compatible with Tripp Lite's WatchDog Service Monitoring and Control
Software (part# WATCHDOGSW)
* Fault-tolerant auto-bypass maintains continuous utility output to
connected equipment, even in cases where the UPS is overloaded or suffers an
internal failure that requires service
* Diagnostic LEDs
* $250,000 Ultimate Lifetime Insurance coverage for conbnected equipment(USA
& Canada only)
* 2-year product warranty
Package Includes
* SU2200XLa On-line Double-Conversion UPS System
* PowerAlert Software and cabling
* Instruction manual with warranty information
* EPO (Emergency Power Off) cabling
DESCRIPCIÓN NOBREAK TRIPP
LITE 2,200VA SU2200XLA
OUTPUT
Output Volt Amp Capacity (VA) 2200
Output kVA capacity (kVA) 2.2
Output Watt Capacity (watts) 1600
Output kW capacity 1.6
Output power factor 0.7
Crest Factor 3:1
Nominal Output Voltage(s) Supported 110v; 120v
Nominal Voltage details 120V default
Frequency compatibility 50 / 60 Hz
Frequency compatibility details Output frequency matches input nominal on
startup, defaults to 60 Hz on cold-start
Output voltage regulation (line mode) +/- 2%
Output voltage regulation (Economy line mode) +/- 10%
Output voltage regulation (Battery mode) +/- 2%
Built-in UPS output receptacles 6 5-15/20R outlet(s); 1 L5-20R outlet(s)
Built-in controllable switched load banks Two switchable three-outlet
5-15/20R load banks
Basic PDU options PDUNV (1U / 2 C19, 12 C13 outlets); PDU1420T (0U / 14
5-15/20R outlets); PDU40TDUAL (0U / 40 5-15/20R outlets)
Metered PDU options PDUMH20 (1U / 13 5-15/20R outlets); PDUMH20AT (1U / 16
5-15/20R outlets)*; PDUMV20 (0U / 16 5-15/20R outlets); PDUMV40 (0U / 32
5-15/20R outlets)
Switched PDU options PDUMH20ATNET (1U / 16 5-15/20R outlets)*; PDUMV20NET
(0U / 24 5-15/20R outlets)
External PDU redundancy options *ATS switch options PDUMH20AT & PDUMH20ATNET
support dual UPS and hot-swappable UPS configurations
Output AC waveform (AC mode) Sine wave
Output AC waveform (battery mode) Sine wave
INPUT
Rated input current (at maximum load) 16A (120V), 17.6A (110V)
Nominal Input Voltage(s) Supported 110V AC; 120V AC
UPS input connection type 5-20P
Input circuit breaker 30A
UPS Input cord length (ft.) 10
UPS Input cord length (m) 3
Recommended Electrical Service 20A 120V
BATTERY
Full load runtime (minutes) 4.5 min. (1600w)
Half load runtime (minutes) 14 min. (800w)
Expandable battery runtime Extended runtime supported via optional external
battery packs
External battery pack compatibility BP48V24-2U (limit 1); BP48V60RT3U (multi-pack
compatible)
DC system voltage (VDC) 48
Battery recharge rate (included batteries) Less than 5 hours from 10% to 90%
Replacement battery cartridge (internal UPS battery replacement) RBC48-SUTWR
Battery Access Battery access door
Battery replacement description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation description Online, double-conversion power
conditioning
Overvoltage correction 2% output voltage regulation during overvoltages to
138
Undervoltage correction 2% output voltage regulation during undervoltages to
80
Severe undervoltage correction 2% output voltage regulation during
undervoltages to 65 (under 70% load only)
LEDS ALARMS & SWITCHES
LED Indicators 14 LEDs indicate line power, online mode, economy/bypass
mode, on-battery, overload, battery low, replace battery and fault status
information - includes 4-LED meter display for load and battery charge level
Alarms Audible alarm indicates UPS startup, power-failure, low-battery,
overload, UPS fault and remote shutdown conditions
Alarm cancel operation Power-fail alarm can be silenced using alarm-cancel
switch
Switches 2 switches control off/on power status and alarm-cancel/self-test
operation
SURGE / NOISE SUPPRESSION
UPS AC suppression joule rating 570
UPS AC suppression response time Instantaneous
UPS Dataline suppression 1 line TEL / DSL or 10Base T Ethernet protection
EMI / RFI AC noise suppression Yes
PHYSICAL
Installation form factors supported with included accessories Tower
Primary form factor Tower
UPS / Power Module dimensions in primary form factor (height x width x depth
/ inches) 10.2 x 9 x 19.5
UPS / Power Module dimensions in primary form factor (height x width x depth
/ cm) 26 x 22.9 x 49.5
UPS / Power Module weight (lbs) 52.7
UPS / Power Module weight (kg) 23.9
UPS Shipping dimensions (height x width x depth / inches) 15.2 x 13 x 24
UPS Shipping dimensions (height x width x depth / cm) 38.7 x 33 x 61
Shipping weight (lbs) 59.5
Shipping weight (kg) 27
UPS housing material Steel
Cooling method Fan
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40
degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees
Celsius
Relative Humidity 0 to 95%, non-condensing
AC mode BTU / hr. (full load) 812.9
AC economy mode BTU / hr. (full load) 347.2
Battery mode BTU / hr. (full load) 885.6
AC economy mode efficiency rating (100% load) 94%
Audible Noise < 45 dB at front side 1m
COMMUNICATIONS
Communications interface USB (HID enabled); DB9 Serial; Contact closure;
EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port description Supports detailed monitoring of UPS and
site power conditions; DB9 port supports RS232 and contact closure
communications
PowerAlert software Included
Communications cable USB and DB9 cabling included
WatchDog compatibility Supports Watchdog application, OS and hard-reboot
restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer to battery power (setpoint) 80V (100% load), 65V ( <70%
load)
High voltage transfer to battery power (setpoint) 138
SPECIAL FEATURES
Cold Start (startup in battery mode during a power failure) Cold-start
operation supported
High availability UPS features Automatic inverter bypass; Hot swappable
batteries
Green & high efficiency features High efficiency economy mode operation;
Individually controllable load banks; Schedulable daily hours of economy
mode operation
CERTIFICATIONS
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada);
Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI); Meets FCC Part
68 / Industrie Canada (telecommunications); ROHS (Reduction of Hazardous
Substances)
WARRANTY
Product Warranty Period (U.S., Canada & Puerto Rico) 2 years
Connected Equipment Insurance (U.S., Canada & Puerto Rico) $250,000
connected equipment insurance
|