Ficha Técnicas NoBreak TRIPP LITE 1400VA OMNISMART1400 click aquí
Tiempo de Respaldo NoBreak TRIPP LITE 1400VA OMNISMART1400 click aquí
Manual de Usuario NoBreak TRIPP LITE 1400VA OMNISMART1400 click aquí
Link a la pagina del Fabricante click aquí
 |
 |
Tripp Lite's OMNI SMART 1400 line interactive UPS
system offers voltage regulation, surge suppression and long lasting battery
support for personal computers, internetworking equipment and other
sensitive electronics. Supports a single entry level PC system for up to 75
minutes during power failures to facilitate a safe shutdown without data
loss. Automatic Voltage Regulation (AVR) circuits regulate brownouts as low
as 75 volts and overvoltages to 147 volts back to normal 120V levels, all
without using battery power. Includes 6 battery supported outlets and 6 foot
AC line cord. USB port enables optional safe unattended system shutdown in
the case of extended power failure as well as continuous UPS and site power
condition monitoring, USB cable included. PowerAlert software available via
free download from www.tripplite.com. Built-in audible alarm and 5 front
panel LEDs indicate status of line power, battery power, battery low/replace,
voltage regulation and overload. 1400VA/940 watt power handling ability
supports multiple entry-level PCs, network workstations, point-of-sale
terminals, small to medium business phone systems, audio/video workstations
and heavily configured home theater systems. Offers 8 minutes battery
runtime with a full load of 1400VA and 24 minutes with a half load of 700VA.
Supports hot swap battery replacement via built-in access panel. 2 year
warranty. $200,000 connected equipment insurance (USA & Canada only).
Key Features
* OMNI SMART 1400 line interactive UPS system offers voltage regulation
and battery support, plus complete AC and dialup/DSL modem line surge
suppression
* Prevents equipment damage, data loss and downtime due to power problems
* Supports a single entry level PC system for up to 75 minutes during power
failures to enable a safe system shutdown
* Supports a max load of 1400VA for 8 minutes
* Supports a half load of 700VA for 24 minutes
* Automatic Voltage Regulation (AVR) circuits correct brownouts as low as 75
and overvoltages as high as 147 volts back to normal 120 volt levels without
using battery power
* Upright tower configuration uses only 66 square inches of floor or desktop
space
* Includes 6 battery supported outlets, 6 foot AC line cord (all NEMA 5-15)
* USB port enables safe unattended shutdown without data loss during
extended power failures, includes USB cable
* USB port supports messaging of UPS and line power status, including on-battery,
low-battery, power-restored, AC line voltage, DC battery voltage and battery
capacity
* USB interface supports timed inverter shutoff after unattended shutdown,
activate self-test and 10 second reboot of connected equipment
* PowerAlert UPS monitoring software available via free download from
www.tripplite.com
* Supports Tripp Lite's WatchDog software application to restore
unresponsive programs by automatically restarting them and rebooting
completely locked computers by automatically switching UPS power off and
back on again
* Built-in audible alarm and 5 front panel LEDs indicate status of line
power, battery power, battery low/replace, voltage regulation and overload
status
* 1400VA/940 watt power handling ability supports multiple entry-level PCs,
network workstations, point-of-sale terminals, small to medium business
phone systems, audio/video equipment stations and heavily configured home
theater systems
* Supports hot-swap battery replacement via built-in battery access panel
* Compatible with 120V/60Hz applications for USA, Canada, Mexico and more
* 2 year manufacturers warranty
* $200,000 connected equipment insurance (USA & Canada only)
Package Includes
* OMNI SMART 1400 UPS System
* USB cable
* Warranty information
* Instruction manual
DESCRIPCIÓN NOBREAK TRIPP
LITE 1400VA OMNISMART1400
OUTPUT
Output Volt Amp Capacity (VA) 1400
Output kVA capacity (kVA) 1.4
Output Watt Capacity (watts) 940
Nominal Output Voltage(s) Supported 115v; 120v
Frequency compatibility 60 Hz
Output voltage regulation (line mode) -18%, +8%
Output voltage regulation (Battery mode) 115V (+/- 5%)
Built-in UPS output receptacles 6 5-15R outlet(s)
Basic PDU options PDU1215 (1U / 13 5-15R outlets); PDUNV (1U / 2 C19, 12 C13
outlets); PDU1415 (0U / 14 5-15R outlets); PDUV15 (0U / 12 5-15R outlets)
Metered PDU options PDUMH15 (1U / 13 5-15R outlets); PDUMH15AT (1U / 8 5-15R
outlets)*; PDUMV15 (0U / 16 5-15R outlets)
Switched PDU options PDUMH15ATNET (1U / 8 5-15R outlets)*; PDUMV15NET (0U /
16 5-15R outlets)
External PDU redundancy options *Auto Transfer Switch features utilizing the
secondary PDU input cord are compatible with Smart Online UPS models only
Output AC waveform (AC mode) Sine wave
Output AC waveform (battery mode) PWM sine wave
INPUT
Rated input current (at maximum load) 9.2A
Nominal Input Voltage(s) Supported 120V AC
UPS input connection type 5-15P
UPS Input cord length (ft.) 6
UPS Input cord length (m) 1.8
Recommended Electrical Service 15A 120V
Input cord length (ft.) 6
Input cord length (m) 1.8
BATTERY
Full load runtime (minutes) 8 min. (940w)
Half load runtime (minutes) 24 min. (470w)
DC system voltage 36V DC
Battery recharge rate (included batteries) Less than 8 hours from 10% to 90%
Replacement battery cartridge (internal UPS battery replacement) RBC53
Battery Access Battery access door
VOLTAGE REGULATION
Voltage regulation description Automatic voltage regulation (AVR)
maintains line power operation with an input voltage range of 75 to 147
Overvoltage correction Input voltages between 128 and 147 are reduced by 12%
Undervoltage correction Input voltages between 93 and 107 are boosted by 14%
Severe undervoltage correction Input voltages between 75 and 92 are boosted
by 30%
LEDS ALARMS & SWITCHES
LED Indicators 5 LEDs indicate line power, battery power, overload,
voltage regulation and battery low/replace status
Alarms Audible alarm indicates power-failure and low-battery conditions
Alarm cancel operation Power-fail alarm can be silenced using alarm-cancel
switch; once silenced, alarm will re-sound to indicate low-battery status
Switches 2 Switches control off/on power status and alarm-cancel/self-test
operation
SURGE / NOISE SUPPRESSION
UPS AC suppression joule rating 480
UPS AC suppression response time Instantaneous
EMI / RFI AC noise suppression Yes
AC suppression joule rating 480
AC suppression response time Instantaneous
PHYSICAL
Installation form factors supported with included accessories Tower
Installation form factors supported with optional accessories Wallmount (use
UPSWM - tower mounting kit)
Primary form factor Tower
UPS / Power Module dimensions in primary form factor (height x width x depth
/ inches) 12.8 x 7.5 x 9.2
UPS / Power Module dimensions in primary form factor (height x width x depth
/ cm) 32.4 x 19 x 23.5
UPS / Power Module weight (lbs) 36.4
UPS / Power Module weight (kg) 16.5
UPS Shipping dimensions (height x width x depth / inches) 18.2 x 12 x 13.8
UPS Shipping dimensions (height x width x depth / cm) 46.4 x 30.5 x 34.9
Shipping weight (lbs) 40
Shipping weight (kg) 18.2
UPS housing material PVC
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40
degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees
Celsius
Relative Humidity 0 to 95%, non-condensing
AC mode BTU / hr. (full load) 204
Battery mode BTU / hr. (full load) 277.9
COMMUNICATIONS
Communications interface USB
PowerAlert software Free download from www.tripplite.com
Communications cable USB cable included
WatchDog compatibility Supports Watchdog application, OS and hard-reboot
restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time 2-4 milliseconds
Low voltage transfer to battery power (setpoint) 75
High voltage transfer to battery power (setpoint) 147
SPECIAL FEATURES
Cold Start (startup in battery mode during a power failure) Cold-start
operation supported
Green & high efficiency features Line interactive UPS with severe brownout
and overvoltage correction
CERTIFICATIONS
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada);
Tested to NOM (Mexico); Meets FCC Part 15 Category B (EMI); ROHS (Reduction
of Hazardous Substances)
WARRANTY
Product Warranty Period (U.S., Canada & Puerto Rico) 2 years
Connected Equipment Insurance (U.S., Canada & Puerto Rico) $200,000
connected equipment insurance
|