Manual de Usuario NoBreak Tripp Lite 3000VA SU3000RTXL3U click aquí
Especificaciones NoBreak Tripp Lite 3000VA SU3000RTXL3U click aquí
Tabla tiempo de Respaldo Tripp Lite 3000VA SU3000RTXL3U click aquí
Link a la pagina del Fabricante click aquí
 |
 |
3000VA on-line, double-conversion UPS system for
critical server, network and telecommunications equipment. 3U rackmount form
factor with an installed depth of 26 inches. Expandable battery runtime with
optional BP72V15-2U (limit 1) and BP72V28RT-3U (multi-pack compatible)
external battery packs. Full time sine wave 110 or 120V output with +/-2%
voltage regulation. Online, double-conversion Uninterruptible Power Supply
(UPS) actively converts raw incoming AC power to DC, then re-converts output
back to completely regulated, filtered AC output. Operates continuously
without using battery power during brownouts to 65V and overvoltages to
150V. Highly efficient operation in optional economy mode saves BTU heat
output and energy costs. NEMA L5-30P input plug. NEMA 5-15, NEMA 5-15/20R
and NEMA L5-30R output receptacles. Network-grade AC surge and noise
suppression. Zero transfer time between AC and battery operation. Network
management interfaces support simultaneous communications via USB port, DB9
serial port and SNMPWEBCARD slot. Built-in DB9 port offers both enhanced RS-232
enabled monitoring data, plus contact closure monitoring ability. HID-compliant
USB interface enables integration with built-in power management and auto
shutdown features of Windows and Mac OS X. Supports simultaneous detailed
monitoring of equipment load levels, self-test data and utility power
conditions via all 3 network interfaces. Includes PowerAlert monitoring
software and complete cabling. Emergency Power Off (EPO) interface.
Integrated two-bank PDU switching supports load shedding and remote reboot
of connected equipment. 3-stage metered current monitoring and battery
charge status LEDs. LED display panel easily rotates for viewing in
rackmount or tower configurations. Dataline surge suppression for dialup,
DSL or network Ethernet connection. Utility power and voltage regulation
LEDs. Audible alarm. Self-test. Fault-tolerant auto-bypass mode. 4-post
rackmount accessories included; 2-9USTAND tower kit and 2POSTRMKITWM 2-post
rackmount accessories available. Field-replaceable, hot-swappable internal
batteries and external battery packs. Attractive all-black color scheme. 2-year
warranty and $250,000 connected equipment insurance; extended warranty and
service contracts available.
Key Features
* SmartOnline high performance UPS system is ideal for critical voice,
data, medical and industrial network applications
* True on-line, double-conversion UPS provides perfectly regulated sine wave
output within 2% of 110/120V (user selectable) under all usage conditions
* Maintains continuous operation through blackouts, voltage fluctuations and
surges with zero transfer time
* Highly efficient operation in optional economy mode setting, saving BTU
heat output and energy costs
* Removes harmonic distortion, fast electrical impulses, frequency
variations and other hard to solve power problems not addressed by other UPS
types
* Corrects line voltage conditions as low as 65V and as high as 150V back to
selectable 110/120V (+/-2%) values
* Standard internal battery set offers 14 minutes runtime at half load
(1200W) and 5 minutes at full load (2400W)
* Expandable battery runtime with optional BP72V15-2U (limit 1) and
BP72V28RT-3U (no limit) external battery packs
* Compact rackmount form factor installs using only 3 rack spaces (3U) with
a maximum installed depth of 26 inches
* Ships with all mounting accessories for 4 post rackmount installation
* Optional 2POSTRMKITWM enables 2 post rackmount installation (not wallmount
compatible)
* Optional 2-9USTAND accessory enables small-footprint upright tower
placement
* Fault tolerant auto-bypass maintains continuous utility output to
connected equipment, even in cases where the UPS suffers internal failure
and requires maintenance
* Network interfaces support simultaneous communications via built-in USB,
DB9 serial / contact-closure and SNMPWEBCARD slot
* HID compliant USB interface enables integration with built-in power
management and auto shutdown features of Windows and Mac OS X
* Included PowerAlert UPS monitoring software supports safe unattended
shutdown, monitoring and control via local connected servers, plus any
number of additional servers over IP
* UPS interface supports on-battery, low-battery, power-restored, AC-voltage,
DC-voltage, output current monitoring, battery charge current, battery
capacity, AC line frequency, timed inverter shutoff, activate self-test,
load bank output power control and remote reboot, UPS nominal voltage
adjustment and UPS line to battery power voltage setpoints
* Built-in Emergency Power Off (EPO) interface with cable
* NEMA L5-30P input plug; NEMA 5-15/20R & L5-30R output receptacles
* Integrated 2 bank switched PDU enables remote outlet management for load
shedding or remote reboot of individual load banks (each bank has four
outlets)
* Front panel LEDs offer current monitoring and battery charge level
information
* UPS ships fully assembled in full compliance with DOT regulations; no time
consuming connection of internal batteries by user required
* Single line TEL/DSL or network ethernet line surge suppression
* 2 year manufacturer's product warranty, $250,000 Ultimate Lifetime
Insurance
Package Includes
* SU3000RTXL3U UPS System
* PowerAlert Software and Cabling
* Mounting hardware for 4 post rack enclosures
* Instruction manual
DESCRIPCIÓN NOBREAK TRIPP
LITE 3000VA SU3000RTXL3U
OUTPUT
Output Volt Amp Capacity (VA) 3000
Output kVA capacity (kVA) 3
Output Watt Capacity (watts) 2400
Output kW capacity 2.4
Output power factor 0.8
Crest Factor 3:1
Nominal Output Voltage(s) Supported 110v; 120v
Nominal Voltage details 120V default
Frequency compatibility 50 / 60 Hz
Frequency compatibility details Output frequency matches input nominal on
startup, defaults to 60 Hz on cold-start
Output voltage regulation (line mode) +/- 2%
Output voltage regulation (Economy line mode) +/- 10%
Output voltage regulation (Battery mode) +/- 2%
Built-in UPS output receptacles 4 5-15R outlet(s); 4 5-15/20R outlet(s); 1
L5-30R outlet(s)
Built-in controllable switched load banks Two switchable four-outlet load
banks, (bank 1 - four 5-15/20R, bank 2 - four 5-15R outlets)
Output circuit breaker 15A branch rated (x2) - each breaker protects 4
outlets, L5-30R is unbreakered
Basic PDU options PDU2430 (1U / 24 5-15R outlets)
Metered PDU options PDUMV30 (0U / 24 5-15/20R outlets)
Switched PDU options PDUMH30NET (2U / 16 5-15/20R outlets); PDUMV30NET (0U /
24 5-15/20R outlets)
External PDU redundancy options *ATS switch options PDUMH20AT & PDUMH20ATNET
support dual UPS and hot-swappable UPS configurations
Output AC waveform (AC mode) Sine wave
Output AC waveform (battery mode) Sine wave
INPUT
Rated input current (at maximum load) 24A
Nominal Input Voltage(s) Supported 110V AC; 120V AC
UPS input connection type L5-30P
Input circuit breaker 40A
UPS Input cord length (ft.) 10
UPS Input cord length (m) 3
Recommended Electrical Service 30A 120V
BATTERY
Full load runtime (minutes) 5 min. (2400w)
Half load runtime (minutes) 14 min. (1200w)
Expandable battery runtime Supports extended runtime with optional external
battery packs
External battery pack compatibility BP72V15-2U (limit 1); BP72V28RT-3U (multi-pack
compatible)
DC system voltage (VDC) 72
Battery recharge rate (included batteries) Less than 6 hours from 10% to 80%
Replacement battery cartridge (internal UPS battery replacement) RBC96-3U (quantity
1)
Battery Access Front panel battery access door
Battery replacement description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation description Online, double-conversion power
conditioning
Overvoltage correction 2% output voltage regulation during overvoltages to
150
Undervoltage correction 2% output voltage regulation during undervoltages to
80
Severe undervoltage correction 2% output voltage regulation during
undervoltages to 65 (under 70% load only)
LEDS ALARMS & SWITCHES
LED Indicators 14 LEDs indicate line power, online mode, economy/bypass
mode, on-battery, overload, battery low, replace battery and fault status
information; 4-LED meter displays load and battery charge levels; LED panel
rotates for viewing in rack/tower formats
Alarms Audible alarm indicates UPS startup, power-failure, low-battery,
overload, UPS fault and remote shutdown conditions
Alarm cancel operation Power-fail alarm can be silenced using alarm-cancel
switch
Switches 2 switches control off/on power status and alarm-cancel/self-test
operation
SURGE / NOISE SUPPRESSION
UPS AC suppression joule rating 510
UPS AC suppression response time Instantaneous
UPS Dataline suppression 1 line TEL / DSL or 10Base T Ethernet protection
EMI / RFI AC noise suppression Yes
PHYSICAL
Installation form factors supported with included accessories 4 post 19
inch rackmount (mounting rail kit included)
Installation form factors supported with optional accessories 2 post
rackmount (2POSTRMKITWM); Tower (2-9USTAND)
Optional mounting accessory notes Wallmount installation not recommended
Primary form factor Rackmount
UPS / Power Module dimensions in primary form factor (height x width x depth
/ inches) 5.2 x 17.8 x 26
UPS / Power Module dimensions in primary form factor (height x width x depth
/ cm) 13.3 x 45.1 x 66
Installed whole system total rack space height (rack spaces) 3U
Secondary form factor Tower (requires 2-9USTAND)
Installed whole system dimensions in secondary form factor (height x width x
depth / inches) 17.8 x 5.2 x 26
UPS dimensions in secondary form factor (height x width x depth / cm) 45.1 x
13.3 x 66
UPS / Power Module weight (lbs) 73.8
UPS / Power Module weight (kg) 33.5
UPS Shipping dimensions (height x width x depth / inches) 11.2 x 23 x 31.5
UPS Shipping dimensions (height x width x depth / cm) 28.6 x 58.4 x 80
Shipping weight (lbs) 112.4
Shipping weight (kg) 51
UPS housing material Steel
Cooling method Fan
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40
degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees
Celsius
Relative Humidity 0 to 95%, non-condensing
AC mode BTU / hr. (full load) 1112.7
AC economy mode BTU / hr. (full load) 520.9
Battery mode BTU / hr. (full load) 1219.3
AC economy mode efficiency rating (100% load) 94%
COMMUNICATIONS
Communications interface USB (HID enabled); DB9 Serial; Contact closure;
EPO (emergency power off); Slot for SNMP/Web interface
Network monitoring port description Supports detailed monitoring of UPS and
site power conditions; DB9 port supports RS232 and contact closure
communications
PowerAlert software Included
Communications cable USB and DB9 cabling included
WatchDog compatibility Supports Watchdog application, OS and hard-reboot
restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer to battery power (setpoint) 80V (100% load), 65V ( <70%
load)
High voltage transfer to battery power (setpoint) 150
SPECIAL FEATURES
Cold Start (startup in battery mode during a power failure) Cold-start
operation supported
High availability UPS features Automatic inverter bypass; Hot swappable
batteries
Green & high efficiency features High efficiency economy mode operation;
Individually controllable load banks; Schedulable daily hours of economy
mode operation
CERTIFICATIONS
UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada);
Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI); Meets FCC Part
68 / Industrie Canada (telecommunications); ROHS (Reduction of Hazardous
Substances)
WARRANTY
Product Warranty Period (U.S., Canada & Puerto Rico) 2 years
Connected Equipment Insurance (U.S., Canada & Puerto Rico) $250,000
connected equipment insurance
|