Manual de Usuario NoBreak Tripp Lite 3000VA SUINT3000RTXL3U click aquí
Especificaciones NoBreak Tripp Lite 3000VA SUINT3000RTXL3U click aquí
Tabla tiempo de Respaldo Tripp Lite 3000VA SUINT3000RTXL3U click aquí
Link a la pagina del Fabricante click aquí
 |
 |
Tripp Lite's SUINT3000RTXL3U UPS System offers
complete power conditioning and battery support for critical fileservers and
internetworking equipment in a versatile 3U rack/tower configuration. Offers
compatibility with 200/208/220/230/240V applications at 50/60Hz. Double
conversion power conditioning process removes line noise, voltage
fluctuations and frequency variations by converting incoming AC to DC, then
back to universally compatible pure sine wave AC output. Standard internal
batteries offer seamless support of connected equipment during power
failures with zero transfer time. Support through extended power failures is
available with the addition of 2U rack/tower compatible battery packs
(BP72V15-2U limit 1/BP72V28-3U multi-pack compatible). Maintains continuous
output over an input range of 160 to 275V without depleting battery
reserves. Brownout support extends to 130V when loaded to 70% or less.
Intelligent DB9 monitoring port works with included PowerAlert software and
cabling for unattended shutdown and remote monitoring of UPS and site power
conditions. Network accessory slot houses optional SNMPWEBCARD accessory for
direct control and monitoring via ethernet. Includes 10 outlets total, 8 of
which are arranged in two customized load management banks that can be
remotely powered off and on via software interface to reboot locked
equipment or extend battery runtime for more critical equipment by shedding
non-essential loads. C20 input connection accepts a variety of detachable
cordsets to match country- or site-specific wall receptacles. 3000VA/2400W
power-handling ability with full CE rating and Class A EMI/RFI rating
supports a wide range of fileservers and internetworking equipment, plus
other sensitive loads requiring full-time power conditioning, regulation and
battery support. Compatible with Tripp Lite's WatchDog system service
software.
Key Features
* True online, double-conversion power conditioning offers enhanced,
network-grade pure sine wave AC power for critical fileservers,
internetworking equipment and sensitive electronics
* Maintains output within 2% of selectable 200/208/220/230/240V at 50/60Hz
(+/-0.05Hz)
* Neutralizes frequency variations, fast electrical impulses, harmonics and
other hard-to-solve power problems not addressed by other UPS types
* Versatile rack/tower format requires only 3 rack spaces (3U) in rackmount
applications; included tower stand set supports upright configuration
* Maintains AC output at near-perfect levels even during long-duration
brownouts as low as 160V and overvoltages to 275V without using battery
power. Brownout support extends to 130V when loaded to 70% or less
* Set of internal batteries supports connected equipment during power
failures for 14 minutes at half load (1500VA/1200W) and 5 minutes at full
load (3000VA/2400W)
* Expandable battery runtime with the addition of external 2U or 3U rack/tower
battery packs (#BP72V15-2U limit 1/BP72V28-3U multi-pack compatible)
* Intelligent DB9 monitoring port communicates site power and UPS status
information including line power status, input voltage, battery status, load
level and more—with full support for applications requiring basic contact
closure power-fail and low-battery messaging
* FREE bundled PowerAlert software compatible with stand-alone and network
operating systems offers unattended shutdown, remote monitoring and control
of UPS system and connected equipment
* Slot for SNMPWEBCARD enables remote monitoring and UPS control via network
management stations or web browser interface (#SNMPWEBCARD)
* Emergency Power Off (EPO) support available; contact Tripp Lite
* Includes 10 outlets (8 IEC320-C13 and 2 IEC320-C19) and one IEC320-C20-to-C19
interconnection cable (additional C13-to-C14 interconnection cables
#P004-006 available )
* Two separate banks of individually controllable outlets enable remote
reboot of locked network equipment without disrupting power to other loads;
accessible via PowerAlert, NMS or enabled web browser—also supports
automatic load shedding of non-essential items to extend battery runtime for
critical equipment
* Compatible with Tripp Lite's WatchDog system service software
* Fault tolerant auto-bypass maintians continuous utility output to
connected equipment, even in cases where the UPS is overloaded or suffers an
internal failure that requires service
* Front panel LEDs and audible alarm provide notification of power status
and full UPS status information
* From the same family as Tripp Lite's SmartOnline SU2200RT2U, named "Editors'
Choice" by PC Magazine, Sept 25, 2001
* CE Certified
* 2-year manufacturer's warranty
Package Includes
* SUINT3000RTXL3U Rack/Tower UPS System
* PowerAlert Software and cabling
* 4 Post Rackmount installation flanges and adjustable depth mounting rails/or
tower stands for upright tower configuration
* (2)6ft IEC320-C13 to IEC320-C14, (1)10ft. IEC320-C19 to IEC320-C20 AC
interconnection cables
* Warranty information and instruction manual
DESCRIPCIÓN NOBREAK TRIPP
LITE 3000VA SUINT3000RTXL3U
OUTPUT
Output Volt Amp Capacity (VA) 3000
Output kVA capacity (kVA) 3
Output Watt Capacity (watts) 2400
Output kW capacity 2.4
Output power factor 0.8
Crest Factor 3:1
Nominal Output Voltage(s) Supported 200v; 220v; 230v; 240v
Nominal Voltage details 230V default
Frequency compatibility 50 / 60 Hz
Frequency compatibility details Output frequency matches input nominal on
startup, defaults to 50 Hz on cold-start
Output voltage regulation (line mode) +/- 2%
Output voltage regulation (Economy line mode) +/- 10%
Output voltage regulation (Battery mode) +/- 2%
Built-in UPS output receptacles 8 C13 outlet(s); 2 C19 outlet(s)
Included output power cables Includes 2 C13 to C14 output power cables
Built-in controllable switched load banks Two switchable four-outlet C13
load banks
Output circuit breaker 10A (x2) each breaker protects 4 C13 outlets, C19 is
unbreakered
Basic PDU options PDUNV (1U / 2 C19, 12 C13 outlets)
Metered PDU options PDUMV20HV (0U / 6 C19, 32 C13 outlets)
Switched PDU options PDUMH20HVNET (1U / 8 C13 outlets); PDUMV20HVNET (0U / 4
C19, 24 C13 outlets)
PDU recommendation notes All noted SWITCHED and METERED PDUs require C19 to
C20 input cable (P036-006 or similar)
Output AC waveform (AC mode) Sine wave
Output AC waveform (battery mode) Sine wave
INPUT
Rated input current (at maximum load) 14.9A (200V),14.3A (208V). 13.1A
(220V), 12.6A (230V), 12.1A (240V)
Nominal Input Voltage(s) Supported 200V AC; 220V AC; 230V AC; 240V AC
UPS input connection type C20 inlet
Input circuit breaker 25A
BATTERY
Full load runtime (minutes) 5 min. (2400w)
Half load runtime (minutes) 14 min. (1200w)
Expandable battery runtime Supports extended runtime with optional external
battery packs
External battery pack compatibility BP72V15-2U (limit 1); BP72V28RT-3U (multi-pack
compatible)
DC system voltage (VDC) 72
Battery recharge rate (included batteries) Less than 6 hours from 10% to 80%
Replacement battery cartridge (internal UPS battery replacement) RBC53 (quantity
2)
Battery Access Front panel battery access door
Battery replacement description Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation description Online, double-conversion power
conditioning
Overvoltage correction 2% output voltage regulation during overvoltages to
275
Undervoltage correction 2% output voltage regulation during undervoltages to
156
Severe undervoltage correction 2% output voltage regulation during
undervoltages to 130 (under 70% load only)
LEDS ALARMS & SWITCHES
LED Indicators 14 LEDs indicate line power, online mode, economy/bypass
mode, on-battery, overload, battery low, replace battery and fault status
information; 4-LED meter displays load and battery charge levels; LED panel
rotates for viewing in rack/tower formats
Alarms Audible alarm indicates UPS startup, power-failure, low-battery,
overload, UPS fault and remote shutdown conditions
Alarm cancel operation Power-fail alarm can be silenced using alarm-cancel
switch
Switches 2 Switches control off/on power status and alarm-cancel/self-test
operation
SURGE / NOISE SUPPRESSION
UPS AC suppression joule rating 480
UPS AC suppression response time Instantaneous
EMI / RFI AC noise suppression Yes
PHYSICAL
Installation form factors supported with included accessories 4 post 19
inch rackmount (mounting rail kit included)
Installation form factors supported with optional accessories 2 post
rackmount (2POSTRMKITWM); Tower (2-9USTAND)
Optional mounting accessory notes Wallmount installation not recommended
Primary form factor Rackmount
UPS / Power Module dimensions in primary form factor (height x width x depth
/ inches) 5.2 x 17.3 x 19.8
UPS / Power Module dimensions in primary form factor (height x width x depth
/ cm) 13.2 x 43.9 x 50.3
Installed whole system total rack space height (rack spaces) 3U
Secondary form factor Tower (requires 2-9USTAND)
Installed whole system dimensions in secondary form factor (height x width x
depth / inches) 17.3 x 5.2 x 19.8
UPS / Power Module weight (lbs) 74.9
UPS / Power Module weight (kg) 34
UPS Shipping dimensions (height x width x depth / inches) 13.3 x 23.8 x 25.8
UPS Shipping dimensions (height x width x depth / cm) 33.8 x 60.5 x 65.5
Shipping weight (lbs) 90.3
Shipping weight (kg) 41
UPS housing material Steel
Cooling method Fan
ENVIRONMENTAL
Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40
degrees Celsius
Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees
Celsius
Relative Humidity 0 to 95%, non-condensing
AC mode BTU / hr. (full load) 1219.3
AC economy mode BTU / hr. (full load) 520.9
Battery mode BTU / hr. (full load) 1328.4
AC economy mode efficiency rating (100% load) 94%
Audible Noise 47dBA At Front Side 1 Meter
COMMUNICATIONS
Communications interface DB9 Serial; Contact closure; Slot for SNMP/Web
interface
Network monitoring port description Supports detailed monitoring of UPS and
site power conditions; DB9 port supports RS232 and contact closure
communications
PowerAlert software Included
Communications cable DB9 cable included
WatchDog compatibility Supports Watchdog application, OS and hard-reboot
restart options for remote applications
LINE / BATTERY TRANSFER
Transfer time No transfer time (0 ms.) in online, double-conversion mode
Low voltage transfer to battery power (setpoint) 160V (100% load), 130V (
<70% load)
High voltage transfer to battery power (setpoint) 275
SPECIAL FEATURES
Cold Start (startup in battery mode during a power failure) Cold-start
operation supported
High availability UPS features Automatic inverter bypass; Hot swappable
batteries
Green & high efficiency features High efficiency economy mode operation
CERTIFICATIONS
UPS Certifications Tested to UL1778 (USA); Tested to CE (EU)
WARRANTY
Product Warranty Period (U.S., Canada & Puerto Rico) 2 years
|